Installation Guidelines

3.3.4Special Measures for Interference-Free Operation

Fitting Quenching

As a rule, inductances such as contactor or relay coils controlled by

Elements to

SIMATIC S5 do not require external quenching elements in the circuit,

Inductances

because the quenching elements are already integrated in the modules.

 

Inductances should only be fitted with quenching elements

 

S when SIMATIC S5 output currents can be switched off by additionally

 

fitted contacts, such as relay contacts. In this case the integrated

 

quenching elements in the modules are no longer effective;

 

S if they are not controlled by SIMATIC S5 modules.

 

You can place freewheel diodes, varistors or RC networks in circuit with

 

inductances.

 

 

Circuitry for DC-Operated

Circuitry for AC-Operated

 

 

Inductances

 

 

 

 

 

 

Inductances

 

 

With Diode

With Zener Diode

With Varistor

With RC Network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3-6 Quenching Circuits for Inductances

System Manual

3-17

C79000-G8576-C199-06