Analog Input/Output Modules

Remove an analog input/output module as follows:

Step

1

2

3

4

Action

Release the upper locking bar on the subrack and swivel it upwards and out.

Slacken the screw in the upper part of the front connector. This causes the front connector to be pressed out of the female connector of the module. Contacts F+ and F- of the enable input at the upper end of the front connector are thus opened first. If the enable input is active, power is removed from the outputs and the module is isolated from the S5 bus.

Swing the front connector out and lift it away from the support pin of the module.

Release the module by rotating the locking pin by 90o at the lower end of the module. You can pull the module out of the subrack with a grip with swivels outwards.

 

 

6

1

 

Module

Front

 

 

Connector

 

 

 

 

Support Mount

 

5

Support Pin

 

 

 

4

 

 

2

 

 

3

 

Figure 9-28 Module with Front Connector

1Screw

2Locking pin

3Support mount

4Support pin

5Grip

6Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of supply and signal lines which are to be connected to the programmable controllers and front connectors of the modules.

Detailed information on cabinet assembly, cabinet ventilation and protective measures can be found in Chapter 3.

System Manual

9-85

C79000-G8576-C199-06

Page 467
Image 467
Siemens S5-135U/155U appendix Module with Front Connector