Siemens S5-135U/155U appendix Maintenance and Repairs, Fans, Follows, Filter Mat

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 106
Image 106

Central Controllers and Expansion Units Power Supply Units

4.3.4Maintenance and Repairs

Lithium Battery The lithium battery should be replaced when a battery failure is indicated. The backup times of the lithium battery are given in the following table:

Ibackup mA

New battery,

backup time in weeks

Battery 3 years old, backup time in weeks

0.25

81.5

64.2

1

27.4

21.6

2

14.5

11.5

3

9.9

7.8

4

7.5

5.9

5

6.0

4.8

Fans

If a fan fails, replace it as quickly as possible. The behavior of the power

 

supply in the event of fan failure is described in Section 4.3.5.

Rechargeable

The rechargeable battery should be replaced at regular intervals (service life

Battery

of 6 years at 40 oC (104 oF) ambient temperature). With a failed power

 

supply and failed battery, the backup times of the rechargeable battery are as

 

follows:

Ibackup mA

Backup time in weeks

0.25

18.8

1

6.3

2

3.4

3

2.3

4

1.7

5

1.4

Filter Mat

The replacement intervals for the filter mat (with the air filter option) depend

 

on the ambient conditions under which the power supply unit is in operation.

4-40

System Manual

C79000-G8576-C199-06

Page 106
Image 106
Siemens S5-135U/155U Maintenance and Repairs, Fans, Supply in the event of fan failure is described in Section, Follows