Siemens S5-135U/155U appendix Programmed, Whose contents are not to be erased, Initial situation

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 229
Image 229

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Inserting

Since the contents of the inserted RAM submodule are erased with each

Programmed

overall reset, proceed as follows when using programmed RAM submodules

Memory

whose contents are not to be erased:

Submodules

Initial situation:

 

 

S The CPU is in the programmable controller.

 

S The power supply of the PLC is switched off.

 

S The mode switch of the CPU is at STOP.

Step

1

2

3

4

5

6

7

8

Action

Insert another, unprogrammed memory submodule in the CPU.

Switch the power supply on.

Carry out an overall reset.

Switch the power supply off.

Remove the unprogrammed memory submodule.

Insert the programmed memory submodule.

Switch the power supply on.

Carry out a reset.

Removing Memory Before removing the RAM submodule, check whether the battery is still in

Submodulesorder: if the battery fault LED on the RAM submodule is lit whilst the PLC supply voltage is switched on, the contents of the RAM submodule will be lost when it is removed.

Initial situation:

SThe CPU is in the RUN state.

Step

1

2

3

Action

Set the CPU mode switch to STOP.

Switch the power supply off.

Remove the memory submodule.