Analog Input/Output Modules

9.3.12Broken Wire Signal

Broken Wire

An open-circuit in the lines to a resistance thermometer is indicated as

Signal in the

follows:

Standard Pt 100

 

Range

 

Broken Wire at

Module Reaction, Encoded Value

Error Bit E

M+

Pt 100

IC+

I

0

0

01)

0

0

1

1

1

0

0

 

1) With the 460 analog input module, the value 0 is also encoded for the intact Pt 100 resistances

 

because the auxiliary circuit is interrupted; the error bit will not be set for these channels.

 

If the mode ªwithout broken wire signalº is selected on the module, an

 

open-circuit of the resistance thermometer is indicated with an overflow.

 

Unassigned channels can be used for voltage or current measurement.

Broken Wire

If a line of the auxiliary circuit (IC+, IC-) is interrupted, the ªnegative range

Signal in the

limitº is encoded for all inputs and the overflow bit is set to ª1.º In the event

Extended Pt 100

of a sensor or measuring line open-circuit, the error bit is additionally set to

Range

ª1º for the relevant channel.

9-22

System Manual

C79000-G8576-C199-06

Page 404
Image 404
Siemens S5-135U/155U appendix Broken Wire Signal, Standard Pt Range, Extended Pt, ª1º for the relevant channel