Siemens S5-135U/155U appendix Inputs, Outputs, Plate of the power supply units

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 87
Image 87

Central Controllers and Expansion Units Power Supply Units

Inputs and

Based on the example of the 6ES5 955-3LF41 power supply unit, the

Outputs

following figure shows the arrangement of inputs and outputs on the front

 

plate of the power supply units:

SIEMENS

AC line 50/60 Hz

Enable

Power supply

 

 

10

AC120V4,5A

 

 

 

 

9

AC230V2,6A

EN

UH

 

3LF42

8

 

 

 

CAUTION!

Voltage

 

 

7

 

 

 

 

 

 

Disconnect

 

 

 

 

 

selector

 

 

6

 

 

before

 

Power

6ES5955-

213 4 5

 

 

removing

 

 

1

2

 

 

 

3

 

 

 

 

 

 

 

power supply!

 

 

 

 

 

 

L1

N

 

 

I

 

 

 

 

 

4

5

I

 

 

 

 

 

 

 

 

 

 

 

Unlock

 

 

 

 

 

 

 

Fan 1

 

 

Voltage Monitor

 

Fan

 

 

Input

 

Fault

Warning

Alarm

DC 24V Ext.

max. AC 250 V/ 3A

 

Voltagelow

Fan1

Fan2 Fan3

Alarm

 

 

 

 

 

 

+

±

 

 

 

 

6

7

8

9

10

11

12 13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unlock

Fan2

Battery

DC 5/15/24V

Internal

 

Warning

Output

DC 24V 2,8A

max. AC 250V/3A

 

Batt.+Fan

3V=40A 5Vo.k. 15Vo.k.

 

 

 

 

MB low

RB low

24Vo.k.

 

 

 

 

 

 

+

 

 

 

 

 

 

Reset

±

+

±

 

 

 

 

 

14

15

16

 

 

17

18

 

 

 

 

 

Unlock

 

 

 

 

Fan3/Res.Batt

 

 

 

 

.

 

 

 

 

Ext.Batt.

DC 4,5V

+

±

Batt. 3,6V/5Ah

Use battery holder C98100-A1155-B21 only!

Replace by trained personnel only!

The following table provides an overview of the labelling and purpose of the inputs and outputs:

ID

Label

 

 

AAC 120V 4.5A AC 230V 2.6A

BEN

CUH

DInput

DC 24V Ext.

EFan Warning max. 250V/3A

FFan Alarm max. 250V/3A

GBattery Warning max. 250V/3A

H3V = 40A

IOutput

DC 24V 2.8A

JExt.Batt. DC 4.5V

Element

Screw terminals 1, 2, 3

Screw terminal 4

Screw terminal 5

Screw terminals 6 and 7

Screw terminals 8, 9, 10 (relay)

Screw terminals 11, 12, 13 (relay)

Screw terminals 14, 15, 16 (relay)

2 test sockets

Screw terminals 17, 18

2 input sockets

Purpose

AC connection and protective conductor

Enable Power Supply

Control input for power supply

Supply for EN

Voltage Monitor

Monitors 24 V load voltage for > 16 V

Indicates failure of a fan

Indicates failure of at least two fans and inadequate air flow; if jumper set accordingly, output enable is the second signal source

Indicates that lithium battery or rechargeable battery has dropped below limit

Current measurement sockets for test purposes only; no continuous operation; linearity range 0.5 V/6.6 A to 3 V/40 A

Enable voltage for I/O modules

Input for an external 4.5 V backup voltage

System Manual

4-21

C79000-G8576-C199-06

Page 87