Monitoring Module

10.1.4Fault Detection

From an address which has been set at switch S1, the data (55H or AAH) is read by the CPU from the monitoring module. This data is to be written back by the CPU to the address set at switch S2. The module inverts the accurate incoming data bit by bit (from 55H to AAH or vice versa) which is read again in the next cycle from the address set at S1.

Data Bus Faults

If the data which has been set on the monitoring module is not returned

 

within the set monitoring time, the module signals a data bus fault.

 

Detectable faults

 

Interruptions of the data lines, short circuits to ground and + 5V, short

 

circuits between adjacent data lines, e.g. DB0-DB1, DB1-DB2 etc.

 

Non-detectable faults

 

Short circuits between even data lines DB0-DB2-DB4-DB6 and between odd

 

data lines DB1-DB3-DB5-DB7.

Address Bus

The addresses which have been set at switches S3 and S4 are only ªlistened

Faults

toº by the monitoring module, i.e. they do not output an acknowledgement

 

signal (RDY/) and are not active on the data bus. If one or both addresses are

 

not accessed again within the monitoring time, the monitoring module

 

signals an address bus fault.

 

Detectable / non-detectable faults

 

The same as for the data bus, if the inverse addresses 85 (55H) and 170

 

(AAH) have been set at the addressing switches S3 and S4 of all monitoring

 

modules.

10-4

System Manual

C79000-G8576-C199-06