Analog Input/Output Modules

Setting the Data Format for the 4 to 20 mA Range

When using the 4 to 20 mA inputs, you can select data representation of 0 to 1023 bits or 256 to 1279 bits by pressing the appropriate switch. You can choose different data formats for all four input channels.

When the voltage or 0 to 20 mA inputs are used, the relevant switches remain at the opposite settings.

Labeling of the switch on the module cover:

 

channel 0

range 4...20 mA

channel 1

 

0...1023

channel 2

 

channel 3

 

1)

range 4...20 mA

channel 3

channel 2

256...1279

otherranges

channel 1

0...1023

channel 0

 

1) It is advisable to mark the selected switch setting in these fields.

Connecting Transducers

!

Transducers are connected to the analog input module via shielded cables of up to 200 m in length. When they are laid separately from power system cables, distances of up to 500 m are possible.

An arbitrary mixture of voltage sensor, current sensor, two-wire and four-wire transducers can be connected. For two-wire transducers, there are four short-circuit protected supply terminals at the front connector.

Caution

To use two-wire transducers, the reference potential (common input) of these channels must be connected to L-. This defeats the isolation between the channels and the supply voltage L+/L-.

Note that the bus interface of the module is activated with 24 V via enable lines F+ and F- at the front connector.

9-48

System Manual

C79000-G8576-C199-06

Page 430
Image 430
Siemens S5-135U/155U appendix Setting the Data Format for the 4 to 20 mA Range, Connecting Transducers