Interface Modules

Connecting the

For one IM 300-5, you can connect up to three EUs to a CC or EU in

EU 184U and

distributed arrangement (see Figures 7-5 and 7-6). The EUs are supplied with

EU 187U

operating voltage via the IMs. Any free connections on the IM 300-5 and the

 

last IM 312-5 require no terminator.

 

 

 

Note

 

The maximum permissible current over each connection of the

 

IM 300-5CA11 is 5 A.

 

 

Connecting the

You can connect up to four EUs to each IM 300-3. The last IM 312-3

EU 183U, EU 185U

requires a terminator.

Connecting the

You can connect up to three ERs to each IM 300-5L (-5LB11). The ERs are

ER 701-1

supplied with operating voltage via the IMs.

 

 

 

Note

 

The maximum permissible current over each connection of the

 

IM 300-5LB11 is 2 A.

 

 

 

The connection of central controller and expansion unit to the IM 300-5LB11

 

is provided exclusively by the 705-0 connecting cable. It is available in two

 

lengths: 0.5 m and 1.5 m (refer to the ordering information for order

 

numbers).

Addressing

When the IM 300s are used in the S5-135U/155U PLC, the input/output

 

modules can be addressed in the normal (P) and extended (O) areas.

 

You may only set module addresses in the EU which are not used in the CC.

 

This applies to both areas.