Analog Input/Output Modules

9.3.3Special Features of the 460 Analog Input Module

 

The 460 analog input module executes integrating processing of the digital

 

input signals; periodic system interference is thus suppressed.

 

You can adapt the process signals, according to the application, to the input

 

level of the analog-to-digital converter of the module with plug-in range

 

cards (resistor dividers or shunt resistors).

Broken Wire

To monitor the sensors connected to the inputs, you can use the

Signal

6ES5 498-1AA11 range card (through-connection card) to implement the

 

ªbroken wire detectionº mode. You can activate broken wire detection for 4

 

or 8 inputs.

 

Each time the input value is about to be encoded, a constant current is briefly

 

(1.6 ms) switched to the input terminals and the resultant current is checked

 

for a limit value. If a digital voltmeter is used to measure the signal at the

 

input, these current pulses may appear to indicate fluctuation of the signal.

 

The encoded value, however, is not affected.

Switching the

If these apparent fluctuations of the signal are disturbing, e.g. during startup,

Tripping Current to

you can switch the tripping current to the inactive state on the 460 analog

the Inactive State

input module: apply + 24 V to pin 24 of the front connector, and 0 V to L-.

 

You must additionally set the mode switch to ªwithout broken wire

 

detection.º

 

In the event of open-circuit of the sensor or its line, the voltage exceeds the

 

limit and a broken wire is indicated (bit 1 in data byte 1). The

 

analog-to-digital converter encodes the value 0.

 

A broken wire signal is only useful when the 6ES5 498-1AA11

 

through-connection card is used. With all other measurement cards, a broken

 

wire signal will result in incorrect reactions. Further details relating to the

 

broken wire signal can be found in Section 9.3.12.

Measuring Range

If the measuring range is exceeded, the overflow bit (bit 2<M>0 of the low

Exceeded

byte) is set.

Cyclic Sampling

You have a choice of the cyclic sampling and selective sampling modes.

 

In the cyclic sampling mode, the module continuously encodes all measured

 

values. The digitized measured values are stored under the channel-related

 

address on the module (the high byte under this address, and the low byte

 

under the next higher address). The measured values can then be read by the

 

module at any time without waiting. When you operate the module in this

 

mode, you can set a module address from 0 to 255.

9-8

System Manual

C79000-G8576-C199-06

Page 390
Image 390
Siemens S5-135U/155U appendix Special Features of the 460 Analog Input Module