Analog Input/Output Modules

9.3.10Connecting Resistance Thermometers in the Standard Pt 100 Range

The series-connected resistance thermometers (up to 8 Pt 100s) are fed with a current of 2.5 mA (IC+/IC-) by a constant current generator. The voltage at the Pt 100's is picked off at measurement inputs M+ and M-. In this mode, the whole temperature range of the Pt 100 (-200 °C to +840 °C) is available. The mode is printed on the cover of the module as follows:

ªresistance thermometer uncompensated full range.º Other voltage sensors can be connected in a floating circuit at the M+/M- inputs of a card which are not assigned to resistance thermometers (voltage range 500 mV).

 

+

 

 

 

 

 

 

 

 

 

 

 

460 Analog Input Module

Pt 100

±

 

 

 

Card 1

 

 

 

M +

 

 

 

 

 

 

 

 

 

 

 

CH0

 

A

 

 

 

 

 

 

 

 

 

 

Range

 

Pt 100

 

 

CH1

 

Card for

MUX

 

 

 

 

 

4 Inputs

 

 

 

 

 

 

6ES5 498-

 

 

 

 

CH2

 

-1AA11

 

 

 

 

 

 

#

 

 

 

 

 

 

Pt 100

 

 

 

 

 

 

 

 

 

CH3

 

 

D

 

 

0...500 mV

 

 

 

 

 

 

 

 

 

 

 

 

Card 2

 

 

UCM

 

CH4

 

 

 

 

0...500 mV

 

 

 

 

 

 

 

 

 

 

UCM

2)

 

Range

 

 

 

 

Card for

 

 

 

 

 

 

4 Inputs

 

 

 

 

 

 

6ES5 498-

 

 

 

 

 

 

-1AA11

 

 

 

 

 

 

1)

 

 

 

 

CH7

 

 

 

Pt 100

 

 

 

I

 

 

 

 

 

 

 

L +

 

 

 

 

 

 

 

 

 

 

IC+

 

L ±

 

 

 

 

const.

 

 

 

 

 

 

2.5 mA

 

 

 

 

 

 

 

0 V Bus

Figure 9-9 Connecting Resistance Thermometers in the Standard Pt 100 Range

1)If no Pt 100 is connected to CH4 to CH7, other voltages and currents can be measured at these channels with cards 6ES5 498-1AA21, 6ES5 498-1AA31, 6ES5 498-1AA41, 6ES5 498-1AA51, 6ES5 498-1AA61, 6ES5 498-1AA71.

2)When cards 6ES5 498-1AA41, 6ES5 498-1AA51 or 6ES5 498-1AA71 are used, a short-circuit jumper is not required.

9-20

System Manual

C79000-G8576-C199-06