CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.1.3Interfaces of the CPU 948

 

This section contains information on the interfaces of the CPU 948.

PG interface SI1

You can use the PG interface on the CPU 948 either via the front connector

 

or via the 923C coordinator module and the S5 bus.

 

 

 

Note

 

Simultaneous operation of the PG interface via the front connector of the

 

CPU 948 and via the 923C coordinator is not possible. Switching the PG

 

online without a job request is already sufficient to operate the interface.

 

Electrically, it is merely a PG interface which can be operated via two

 

different terminals.

 

 

 

The connection to the PG can be established in every operational state of the

 

CPU.

Second Interface

You can optionally use the second interface of the CPU 948 -3UA13 or the

SI2

CPU 948 -3UA23 as:

 

S A PG interface (for PG and operator panels)

 

S Interface for the RK 512 computer link

 

S Interface for data transmission with procedures 3964/3964R

 

S Interface for data transmission with the ªopen driverº

 

S Interface for data transmission via the SINEC L1 bus.

 

To utilize the second interface as the PG interface, you need the

 

S PG submodule.

System Manual

C79000-G8576-C199-06

You need one of the following interface submodules for the RK 512 computer link, for data transmission with procedures 3964/3964R and for data transmission with the ªopen driverº:

SV.24 submodule (RS 232C)

STTY submodule

SRS422 A/485 submodule (only in the RS422 A module).

To utilize the second interface for data transmission via the SINEC L1 bus, you need the

SSINEC L1 submodule.

The CPU 948 -3UA13 or the CPU 948 -3UA23 is delivered without an interface submodule. You can operate the CPU 948 -3UA13 or the CPU 948 -3UA23 without an integral interface submodule. The opening to accept a submodule in the front plate is closed by a cover. Only remove the cover to fit an interface submodule.

A description of interface submodules can be found in Section 5.11, and the order numbers in the ordering information.

A detailed description of the second interface can be found in the CPU 928B/CPU 948 Communication Manual.