9.7.8Connecting Loads to the 470 Analog Output Module

The voltage at the load is measured at a high resistance via the sensor lines (S+/S-) of voltage output QV, so that voltage drops on the load lines do not falsify the load voltages. Lines S+(x) and S-(x) should therefore be directly connected to the load (four-wire circuit). The voltage drops on the lines from QV(x) to the load and from the load to MANA must not exceed 3 V.

QV(x)

 

 

S+(x)

 

+

 

 

 

 

Load (Voltage)

S ± (x)

 

±

 

 

QI (x) I

+

Load (Current)

 

 

 

±

MANA

Figure 9-39 Connecting Loads

QV(x)

Voltage output, voltage on Channels 0 to 7

QI(x)

Current output, current on Channels 0 to 7

S+(x)

Sensor line (+) for Channels 0 to 7

S- (x)

Sensor line (-) for Channels 0 to 7

MANA

Ground terminal for the analog section

Connecting Loads When current and voltage outputs are used on the 470-4UA/-4UC... analog

to Current and output modules, connect the loads as follows:

Voltage Outputs

QV0

QV1

QV2

QV3

 

QV4

 

 

 

 

 

 

Jumper

Jumper

S+0

S+1

S+2

S+3

 

S+4

 

+

 

+

+

 

 

 

±

S±1

±

±

 

S±4

 

S±0

S±2

S±3

 

 

QI0

QI1

QI2

QI3

 

QI4

_

+

 

+

+

+

 

 

±

 

±

±

±

Jumper

Jumper

MANA

 

 

 

 

 

 

 

 

 

MANA

 

MANA

 

 

 

 

Current

 

Not Current

 

 

 

Output

 

and Not Voltage

 

 

 

Only

 

Output

 

Figure 9-40 Connecting Loads

System Manual

9-109

C79000-G8576-C199-06

Page 491