Central Controllers and Expansion Units Power Supply Units

4.3.6Technical Specifications of the Power Supply Units

Important for the USA and Canada

The following approval has been obtained:

UL-Recognition-Mark (for USA)

Underwriters Laboratories (UL) to

Standard UL 508, Report E 143289

CUL-Recognition-Mark (for Canada) to

Canadian National Standard C 22.2, No. 142, Report E 143289

6ES5 955-3LC42

6ES5 955-3LF42

Safety Specifications

The power supply units comply with safety specifications VDE 0805 / EN 60950 / IEC 950 / VDE 0160 and VDE 0106 Part 101.

Shock protection

Data for EMC in the installed state

Safe isolation

only insured in the installed state

see technical specifications of the S5-135U/155U CC

is ensured.

Input

Rated input voltage

Rated input frequency

Input current Ii/p

at rated loed and rated Vi/p = 120V

=230V Peak inrush current I i/p max

I@t value of inrush current

Efficiency at rated load (with fans) and Vi/p

¢230/120 V AC

Max. heat dissipation at rated load at Vo/p1, Vo/p2, Vo/p3 (with fans)

Efficiency at rated load (without fans) and Vi/p ¢ 230/120 V AC

Max. heat dissipation (without fans)

Stored energy time during power failure at rated load and

Vi/p ¢ 187/93 V AC (adjustable)

Input fuse

External battery supply

120 V (93-132 V) AC

230 V (187-264 V) AC

50/60 Hz (47-63 Hz)

2.5Arms

1.5Arms

26 A for 2 s, otherwise < 5 A (repetition rate 100 secs)

4A@s > 0.63

80W

0.70

53 W

>20 ms

20ms

5ms

Wickmann G 19343-T4A/250V,

500A@s

4.5 V

120 V (93-132 V) AC

230 V (187-264 V) AC

50/60 Hz (47-63 Hz)

4.5Arms

2.6Arms

25 A for 2 ms (repetition rate 100 secs)

5.2A@s

> 0.68

147W

0.71

123 W

>20 ms

20ms

5ms

Wickmann G 19340-8A/250V,

200A@s

4.5 V

System Manual

4-51

C79000-G8576-C199-06

Page 117
Image 117
Siemens S5-135U/155U appendix Technical Specifications of the Power Supply Units, Input