Siemens S5-135U/155U appendix Other Faults, LEDs Possible Cause Action

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 103
Image 103

Central Controllers and Expansion Units Power Supply Units

Other Faults

Other faults can be indicated by the green LEDs on the front plate going off.

LEDs

Possible Cause

Action

Green LEDs go off and the power supply fails.

The Enable jumper is

Check the jumper.

out of place

 

Latching Off-switching

Switch the supply voltage off and on

by overvoltage at

again. If this does not clear the fault,

output

there is an internal fault.

 

 

Internal fault in the

Send in the PSU for repair.

PSU

 

 

 

Base load too low

Increase the base load

 

 

System Manual