6ES5 470-4UA12, 6ES5 470-4UB12 and 6ES5 470-4UC12 Analog Output Modules

Rated output ranges

±6ES5 470-4UA12

±6ES5 470-4UB12

±6ES5 470-4UC12

Number of outputs

Isolation

Measured value representation

Linearity in the range of $1024 units

Operational error limits (0 to 60 oC)

Temperature coefficient for voltage and current outputs

Permissibleoverrange

Fault current at voltage output

No-load voltage at current output

Load impedance

±at voltage output

±at current output

Delay between data transfer and analog value output to > 99%

Capacitive load including line capacity for -4UA12 from version 03 and

for -4UB12 and -4UC12 from version 04:

Permissible voltage drop on voltage output lines

Power supply

±Digital section from system bus

±Analog section from load voltage

±Enabling for module, F+/F-

Permissible potential difference between reference poten- tial of the load and housing (UCM)

Voltage test to VDE 0160

Surge voltage test to IEC 255-4

0 to $10 V and 0 to 20 mA parallel for $1024 units $10 V for $1024 units

1 to 5 V and 4 to 20 mA parallel for 0 to 1024 units

8 voltage and current outputs each, no-load and short-circuit-proof

Yes 8 outputs with respect to Mext , M and L+/L±

12-bit (two's complement)

$2 LSB = $ 0.2 %

$0.6 %

1 x 10±4/K

Approx. 25 % ($ 1024 to $ 1272 units)

Approx. 25 mA

Approx. 18 V

w3.3 kW v 300 W

v 5ms

100 nF max.

1 mF max.

$0.3 V at maximum output voltage

5 V $ 5 %; approx. 250 mA

24 V; 200 to 400 mA

24 V; approx. 7 mA

25 V AC / 60 V DC max.

Between outputs and housing tested at 500 V AC

Between outputs and L±: Vp = 1 kV; 1,2/50 ms