Multiprocessor Operation/Coordinators

 

The individual actions are explained in more detail in the following.

Step 1

Setting the number of occupied CPU slots on the coordinator:

 

 

 

 

 

923A Coordinator

 

 

 

 

Number of CPUs used

Jumper(s) at EP 62

 

 

 

 

2

7 - 10; 8 - 9 1)

 

3

7 -10

 

 

 

 

4

8 - 9

 

 

 

 

 

923C Coordinator

 

 

 

Coded by inserting only one DIL switch S1.4, S1.5 or S1.6 in the front plate recess: (see Figure 6-2)

DIL S.

S1.1

S1.2

S1.3

S1.4

S1.5

S1.6

on

x

off

x x x

x x

Effect

±

±

Enable test mode

No. of occupied CPU slots = 2 1) No. of occupied CPU slots = 3 No. of occupied CPU slots = 4

1)Setting when delivered

Step 2

Setting the communication flag areas:

IF ...

THEN ...

you use communication flag areas on CPs (please consult the relevant manuals),

you must mask out these areas (blocks) on the coordinator without fail, to avoid duplicated addressing of the communication memory.

The 256 communication flag bytes can be masked out in groups of 32. You do this by removing jumpers at coding socket EP 7 on Coordinator A (see Figure 6-1 for location) or EP 60 on Coordinator C (see Figure 6-2).

6-6

System Manual

C79000-G8576-C199-06