Analog Input/Output Modules

Configuring

You must observe the following when configuring systems:

Switching on

Switching off

At the latest 100 ms after power-up of the PLC, the voltage must be present at the enable inputs of the I/O modules.

When the PLC has been switched off, the voltage at the enable inputs of the I/O modules must still be present as long as the internal 5 V voltage is present.

Switching off the

CC

Separate or Common Shutdown of the CC/EU and Load Power Supply

You should observe the following instructions for switching off CCs and equipment for supplying power to the enable inputs.

When there is a need to switch off the load power supply separately without affecting the enabling of modules, there are the following possibilities for producing the enable voltage. These exist even when the load power supply is used without an additional capacitor and common shutdown.

S230 V AC supply for CC/EU and load power supply

a)

b)

Battery

 

±951

I/O Modules

c)

 

 

F+

 

CC/EU

L+

 

 

 

Power Supply

L+

 

 

 

230 V AC

 

 

Load Power Supply 24V

 

Supply for the enable inputs from:

a)6ES5 951-4LB11 load power supply

b)Battery

c)Terminals for 24 V on the front plate of the power supply

9-6

System Manual

C79000-G8576-C199-06

Page 388
Image 388
Siemens S5-135U/155U appendix Configuring, You must observe the following when configuring systems