Siemens S5-135U/155U appendix You must match the IM 304 to the cable length with jumper

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 305
Image 305

Interface Modules

7.3.2Modes/Jumper Assignments of the IM 304

You must match the IM 304 to the cable length with jumper X11.

 

 

Jumper Plug X11

 

 

 

9 7 5 3 1

9 7 5 3 1

9 7 5 3 1

9 7 5 3 1

9 7 5 3 1

Jumper

*)

 

 

 

 

Location

 

 

 

 

 

10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

Cable Length

10m max.

100m max.

100 to 250m

250 to 450m

450 to 600m

*) This setting is only permissible for IM 304 - IM 324R communication in the S5-155H PLC.

Jumper Assignments

The longest communication path, i.e. the sum of cable lengths at interface of X3 or X4, is governed by the location of jumper X11.

LED2

Jumper X21/X22 set to OFF if no expansion unit is connected.

LED1

X3

X4

X22

OFF ON

ON

OFF

ON

OFF

S3

1

X21 2

3

X14

9 7 5 3 1

 

10 8 6 4 2

X11

X13

X12 3 2 1

X15

X1

1

2

3

X2

Figure 7-12 Location of Jumpers on the IM 304 (when Delivered)