Analog Input/Output Modules

9.7.3Special Features of the 470 Analog Output Module

BASP (Output

The BASP signal is not interpreted by the 470 analog output module. Once

Inhibit)

output, a value is retained.

Function Block

You can output analog values to the process via analog output modules with a

 

function block from the ªbasic functionsº package.

9.7.4Setting the Module Address

 

You set the module address on the addressing switch. This also establishes

 

the necessary assignments between user program and process connection.

 

The module address is the sum of the decimal significances of the switch

 

rockers in the On setting (￿).

 

One data word = two data bytes is required to process an input or an output.

 

A module with 8 inputs or outputs reserves 16 byte addresses.

Labeling Field

You can affix the adhesive label with the desired module address on a free

 

labeling field under the addressing switch.

 

The switch rockers to be set for the module address specified as a decimal

 

number (address bit ADB) are marked by dots on the label.

 

Press the individual rockers of the addressing switch downwards with a

 

ballpoint pen or similar object, but not a pencil.

On Setting

(Switch Pressed)

Address (Decimal)

128

64

32

16

8

4

2

1

ADB7

ADB6

ADB5

ADB4

ADB3

ADB2

ADB1

ADB0

Addressing Switch

Free Field for Label with Module Address and marked Switch Settngs

Decimal Signification of the Address Bit

Address Bit

ADB0 and ADB1 are not assigned

ADB2 is not connected

Figure 9-36 Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is independent of the slot.

9-102

System Manual

C79000-G8576-C199-06