Digital Input/Output Modules

8.4.176ES5 458-4UA12 Digital Output Module

Rated supply voltage L

Number of outputs

Isolation

Range for supply voltage

Fusing

Output

Service life of contacts

Switching capacity with resistive load with RC element module without RC element module

Switching current with inductive load

with RC element module and external suppressor circuit

Switching current for lamps

Switching frequency with resistive load

with inductive load

24 V DC

16

Yes, 16 outputs

20 to 30 V DC

16 x 1 A, slow 1)

Relay contacts

108 cycles

60 V DC/48 V AC, 0.5 A 2)

60 V DC/48 V AC, 70 mA

0.5 A max.

0.1 A max. with RC element module

100 Hz max. (pick-up 1 ms, drop-out 1 ms) 10 Hz max. up to 50 mA,

2 Hz max. up to 0.3 A,

0.5 Hz max. up to 0.5 A

Coincidence factor (total load capability)

Permissible line length

100 %

400 m max., unshielded

Power supply

Digital section from system bus

Current consumption from L+/L±

Power dissipation (rated operation)

5 V, 80 mA typical

200 mA typical

5.2 W

Enable input (F+/F±)

Rated input voltage

Input voltage

for logic 1 for logic 0

Rated input current

Permissible line length

Voltage test to VDE 0160

24 V DC

13 to 33 V ±33 to 5 V

5 mA

200 m max.

Between two groups: 500 V AC

Between group and ground point: AC 500 V

Mechanicalspecifications

Dimensions (W x H x D)

Weight

20 mm x 255 mm x 195 mm

Approx. 0.45 kg

1)The fuse does not protect the contacts. The relay must be replaced after an overload.

2)50 V/0.5 A max. resistive load for UL

8-64

System Manual

C79000-G8576-C199-06

Page 376