Siemens S5-135U/155U appendix Basic Functions, Monitoring, Signaling

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 86
Image 86

Central Controllers and Expansion Units Power Supply Units

Basic Functions

The power supply units offer the following functions:

 

S

System power supply

 

 

All the system voltages required for operation of the modules in a CC or

 

 

EU are supplied.

 

S Power supply for backup (in the CC and EU 185):

 

 

A lithium battery or an external battery ensure data backup when the

 

 

system voltage is switched off or fails.

 

 

± The lithium battery remains in the CC/EU and ensures backup, even

 

 

during replacement of the power supply unit

 

 

± Instead of the lithium battery, an external battery can be connected for

 

 

data backup purposes. Situated on the front plate of the power supply

 

 

unit are two sockets to connect an external battery.

 

The rechargeable battery (in the power supply) continues to back up while

 

either the lithium battery or external battery is being replaced or fails,

 

ensuring that no data are lost.

 

S

Heat removal

 

 

Three independent fans which are individually replaceable during

 

 

operation remove the dissipated power. If a fan fails, the supply voltage

 

 

for this fan is switched off and the other two fans continue operation at

 

 

increased speed.

Monitoring

The power supply units contain monitoring functions to detect the following

Functions

faults:

 

S Failure of system voltage

 

S Failure of output voltages

 

S Failure of an externally applied 24 V DC load voltage (voltage monitor)

 

S Fan failure or inadequate air flow

 

S

Lithium battery failure

 

S

Rechargeable battery failure

 

In this context, a voltage failure is equivalent to a drop of the monitored

 

voltage below a preset limit (see Section 4.3.6 of the Technical

 

Specifications).

Signaling

The failure of a monitored function is signaled by the power supply units:

Functions

S

via LED indicators on the front plate;

 

S via relays with which signaling circuits can be switched;

S via signals to the S5 bus.

4-20

System Manual

C79000-G8576-C199-06

Page 86
Image 86
Siemens S5-135U/155U appendix Basic Functions, Monitoring, Signaling