Interface Modules

Purpose of the

Jumpers

Function

Interface X3/X4

±Switched on

±Switched off 1)

ªI/Os not readyº message relayed

±no

±yes

ªI/Os not readyº message when

±1 interface not ready

±2 interfaces not ready

Set cable length between 304 / 314

±0 to 100 m

±100 to 250 m

±250 to 450 m

±450 to 600 m

Jumper Settings

X22/X21 at ªONº X22/X21 at ªOFFº

X15 no jumpers

X15 jumper 1-2

X14 jumper 1-2

X14 jumper 2-3

X11

Jumper 3-4

Jumper 5-6

Jumper 7-8

Jumper 9-10

ON

OFF

ON

OFF

1

2

3

1

2

3

1

2

3

1

2

3

9 7 5 3 1

10 8 6 4 2

1)Jumper X22 is assigned to interface X3. Jumper X21 is assigned to interface X4

All other jumpers and switches must remain at the factory settings.