4.3.3Fault Indications/Fault Diagnostics

 

This section explains where and how faults are indicated, and how to

 

interpret the LEDs.

Where are Faults

Faults of the system power supply, load power supply, battery supply and

Indicated?

fans are indicated by LEDs on the front plate of the power supply unit.

How are Faults

When all monitoring circuits are switched on (jumper settings), the following

Indicated and

indications can appear:

Interpreted?

 

LED Indication

Cause

Action

ªVoltage lowº LED lights up.

ªMB lowº LED lights up.

ªRB lowº LED lights up.

The voltage at the voltage monitor is less than 14 V.

The lithium battery has failed or the

Replace backup

battery compartment is faulty.

battery or battery

(Precondition: no external bty voltage

compartment

is present).

 

 

 

The rechargeable battery has failed.

Replace

 

rechargeable

 

battery

 

 

ªFan 1º LED lights up.

The speed of Fan 1 has dropped or

 

Fan 1 has stopped.

 

 

ªFan 2º LED lights up.

The speed of Fan 2 has dropped or

 

Fan 2 has stopped.

 

 

ªFan 3º LED lights up.

The speed of Fan 3 has dropped or

 

Fan 3 has stopped.

 

 

At least 2 ªFanº LEDs light

At least 2 fans have failed.

up as well as the ªAlarmº

 

LED.

 

 

 

All 3 ªFanº LEDs flash and

The air flow is inadequate.

the ªAlarmº LED lights up.

 

 

 

Replace fan

Replace fan

Replace fan

Replace fan

Replace filter mat

The fan error is indicated approximately 6 s after the monitoring circuits are switched on or 6 s after a reset is performed.