Analog Input/Output Modules

Example:

(Special case) The temperature of the busbar of an electroplating bath is to be measured with an uninsulated thermocouple.

Sensor,

 

 

Analog Input Module

 

 

 

Not Isolated

M+

 

 

 

 

 

+

 

 

A

 

 

MUX

U E

 

 

 

 

 

±

 

 

 

Range

 

 

 

 

 

 

Card for

 

 

 

4 Inputs

 

+

 

 

#

U CM

 

 

 

 

 

±

 

 

 

 

 

 

D

 

 

U CM

0 V Bus

 

 

 

Figure 9-7 Measuring Circuit without Equipotential Bonding Conductor for the 460 Analog Input Module

The potential of the busbar with respect to the reference potential of the module is, for example, 24 V DC. A 460 analog input module with isolated input is used (UCM = 60 V AC/75 V DC). An equipotential bonding conductor must not be laid here because it would short-circuit the busbar.

9-18

System Manual

C79000-G8576-C199-06

Page 400
Image 400
Siemens S5-135U/155U appendix Mux