Analog Input/Output Modules

9.6.9Technical Specifications

6ES5 466-3LA11 Analog Input Modules

Input ranges

0-20 mA; 4-20 mA; "20 mA; 0-1.25 V; 0-2.5 V; 0-5 V;

1-5 V; 0-10 V;

"1.25 V; "2.5 V; "5 V; "10 V

Number of inputs

16 single or 8 differential inputs in groups of

4 or 2 channels (selectable) voltage or current measurement

Measuring principle

Conversion time

Isolation

Permissible isolation between sensor ref. potential and central ground point

Supply voltage internal external

Current consumption, internal

Encoding time per measured value

Duration of cyclic sampling (cycle time)

for 8 measured values for 16 measured values

Input resistance

voltage measuring range current measuring range

Type of circuit for sensors

Digital representation of the input signal

Max. permissible input voltage without destruction

Interference voltage suppression common-mode interfer- ence (Vpp = 1 V)

Basic error limits

±voltage ranges except for 0-1.25 V; $1.25 V

±current ranges and 0-1.25 V; $1.25 V

Instantaneous value encoding

25ms typical (per channel) Yes

25V AC/60 V DC max.

+5 V +/- 5 %

None

0.7A typical 250 ms

2 ms max.

4 ms max.

w10 M W

125 W

Two-wire circuit

Selectable, following types of representation:

±12-bit two's complement

±11-bit value with sign

±12-bit binary

$30 V max. (static) or

$75 V (pulse for 1 ms max. and duty ratio 1:20)

70 dB min.

0.1%

0.2%