Monitoring Module

10.3.2Setting the Address Switches S1, S2, S3, S4

The addresses are set as one-byte addresses as in the case of I/O modules.

8 7 6 5 4 3 2 1

OFF

ON

ADB 0 Significance

1

ADB 1 Significance

2

ADB 2 Significance

4

ADB 3

Significance

8

ADB 4

Significance 16

ADB 5 Significance 32

ADB 6 Significance 64

ADB 7 Significance 128

The significance of the rockers pressed down to ON at the switches must be added.

Example

Address 85 is to be set.

 

 

 

rockers to be pressed down to ON

Significance

 

 

 

1 (ADB 0)

1

 

 

 

3 (ADB 2)

4

 

 

 

5 (ADB 4)

16

 

 

 

7 (ADB 6)

64

 

 

 

 

85

8 7 6 5 4 3 2 1

OFF

ON

10-12

System Manual

C79000-G8576-C199-06

Page 508
Image 508