Siemens S5-135U/155U appendix Jumper Comm. Flag Byte Address, Examples

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 269
Image 269

Multiprocessor Operation/Coordinators

16

 

 

 

9

 

8

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

8

9

16

 

EP 7

 

EP 60

When the unit is delivered, all communication flag areas are activated (see above):

On Coordinator A

by jumpers at EP 7

On Coordinator C

by jumpers at EP 60

Jumper

Comm. Flag Byte

Address

 

8 - 9

 

0

to

31

F200H

to

F21FH

 

7 - 10

 

32

to

63

F220H

to

F23FH

 

6 - 11

 

64

to

95

F240H

to

F25FH

 

5 - 12

 

96

to

127

F260H

to

F27FH

 

4 - 13

 

128

to

159

F280H

to

F29FH

 

3 - 14

 

160

to

191

F2A0H

to

F2BFH

 

2 - 15

 

192

to

223

F2C0H

to

F2DFH

 

1 - 16

 

224

to

255

F2E0H

to

F2FFH

 

Jumper inserted:

 

area activated (coordinator

 

 

 

 

 

 

 

acknowledges in this area)

 

 

 

 

Jumper not inserted:

 

area masked out (coordinator

 

 

 

 

 

 

 

does not acknowledge in this area)

 

 

Examples

You wish to mask out the four communication flag areas with the highest

 

addresses on COR A:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

9

 

 

 

 

EP7

18

Address F200H to F27FH

Activated (Jumper Inserted)

Address F280H to F2FFH

Masked Out (Jumper Open)

Figure 6-3 Example of Addressing the Communication Memory on COR A

System Manual

6-7

C79000-G8576-C199-06

Page 269
Image 269
Siemens S5-135U/155U appendix Jumper Comm. Flag Byte Address, Examples