CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The module must be inserted at the correct slot in the central controller. The

 

backup battery must be fitted and in order for the CPU to start.

Overall Reset

 

 

 

 

 

 

 

 

Step

Action

Result

 

 

 

 

1

2

Set the mode switch to STOP

Switch the system voltage on.

The following LEDs must light up on the CPU:

±Red STOP LED (flashing rapidly)

±Red BASP LED

3

Hold the MC1) switch in the OVERALL RESET setting and simultaneously set the mode switch from STOP to RUN.

The red STOP LED is now permanently lit.

1)MC: Momentary-contact

Reset

Step

1

2

Action

Result

 

 

Set the mode switch to STOP.

 

 

 

Hold the MC switch in the

± Red STOP LED goes off

RESET setting and

± Green RUN LED lights up

simultaneously set the mode

± Red BASP LED goes off

switch from STOP to RUN.

The CPU is now in the RUN state

 

 

but still has no user program.

 

 

Restart

You can also carry out a manual restart of the CPU 928-3UA21 with the

 

mode switch. The CPU 928 Programming Guide will indicate when a manual

 

restart is permissible.

Step

1

Action

Set the mode switch from STOP to RUN.

Result

±Red STOP LED goes off

±Green RUN LED lights up

±Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user program in single-processor operation can serve to establish whether the CPU is operating without errors.