6.3Coordinator Modes

The Stop State

If, when the supply voltage is switched on, the coordinator mode switch is at

 

STOP or another stop request is pending, the CPUs remain in the Stop state.

Startup

AUTOMATIC RESET or

 

AUTOMATIC RESTART

 

If, when the supply voltage is switched on, the coordinator mode switch is at

 

RUN, an AUTOMATIC RESET or AUTOMATIC RESTART (depending on

 

DX 0 setting) will take place as long as the mode switches of the CPUs are

 

also at RUN and the PLC was previously in cyclic operation.

 

MANUAL START

 

When you set the coordinator mode switch from STOP to RUN, the CPUs

 

will execute a start if this was already prepared at all CPUs by appropriate

 

switch actuation, i.e. the CPUs are in the wait state. As required by the user,

 

the type of start can be the same for all CPUs or arbitrarily different.

 

After the start synchronization by the system programs, the CPUs

 

simultaneously go to RUN (cyclic operation).

Normal Operation

The transition of individual CPUs is synchronized - as long as the preset

and Stop in the

ªstart synchronizationº in the relevant CPUs has not been changed by DX 0

Event of Faults

programming - i.e. only when each CPU has ended its start do all CPUs

 

jointly go to cyclic program processing.

 

If the coordinator mode switch is at the RUN setting and one CPU goes to

 

the Stop state, all the other CPUs also go to the Stop state. The red STOP

 

LED(s) on the CPU(s) causing the Stop state flash slowly; the STOP LEDs of

 

the other CPUs are continuously lit.

 

Apart from any indication with fault LEDs on the CPU which is the cause, all

 

CPUs emit the BASP (output inhibit) signal.