Digital Input/Output Modules

8.4.136ES5 455-4UA12 Digital Output Module

Rated supply voltage L

Number of outputs

Isolation

Range for supply voltage

Fusing

Output voltage

for logic 1 for logic 0

Residual current at logic 0

Switching current (resistive, inductive load) ventilated

not ventilated

Switching current for lamps ventilated

not ventilated

Max. inrush current for

3 ms

20 ms

50 ms

Permissible line length

24 to 60 V AC (47 to 63 Hz)

16, conditional short-circuit protection 1)

Yes, 2 groups of per 8 outputs

20 to 72 V AC

6.3 A, fast; 1 fuse per 4 outputs

L± 1.5 V min.

7.5V max. 5 mA max.

40 mA to 2 A; 6 A max. per 4 outputs 40 mA to 1 A; 4 A max. per 4 outputs

40 mA to 2 A; 2.5 A max. per 4 outputs 40 mA to 1 A; 2.5 A max. per 4 outputs

25A/group

15A/group

13A/group

300 m max. unshielded

Power supply

Digital section from system bus

Power dissipation (rated operation)

Enable input (F+/F±)

Voltage test to VDE 0160

5 V, 100 mA typical

39.0 W

Jumper in front connector

Between two groups: 2000 V AC

Between group and ground point: 1500 V AC

Mechanicalspecifications

Dimensions (W x H x D)

Weight

1)Protected by a fuse.

40 mm x 255 mm x 195 mm

Approx. 0.7 kg

8-56

System Manual

C79000-G8576-C199-06

Page 368
Image 368