Analog Input/Output Modules

The channels have the following designations on the module:

Channel 0:

M0 +

 

M0 ±

Channel 1:

M1 +

 

M1 ±

:

:

Channel 7:

M7 +

 

M7 ±

Channels are arranged in groups of four, for which you can set separate measuring ranges:

Channel group I: Channels 0 to 3

Channel group II: Channels 4 to 7

The following figure shows the connection of sensors to the module.

You must observe the following condition:

UE + UCM < 12 V

(i.e. the sum of the set voltage range and common-mode voltage must be less than 12 V; current measuring ranges correspond to a voltage of 2.5 V).

 

 

Analog Input Module

 

 

M+

+

 

 

UE2

 

±

 

 

 

+

 

MUX

±

 

M+

 

 

UCM2

+

 

U E1

 

±

 

 

 

+

 

U

±

0 Vext

CM1

 

 

 

 

UISO

 

 

0 V Bus

UE1/2: Input Voltage

U CM1/2: Common-Mode Voltage

UISO: Potential Difference

:Equipotential; this potential is established by the sensor reference potential (external reference potential)

Figure 9-31 Connecting Sensors to the 466 Analog Input Module (DifferentialMeasurement)

9-90

System Manual

C79000-G8576-C199-06