Siemens S5-135U/155U appendix Replacing Filter Mat Inadequate Air, Flow

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 112
Image 112

Central Controllers and Expansion Units Power Supply Units

Replacing the

Filter Mat

Inadequate Air

If the filter mat is clogged and the power supply unit no longer receives

Flow

sufficient air, the ªAlarmº LED lights up, LEDs for ªFan 1,º ªFan 2º and

 

ªFan 3º flash and the ªAlarmº relay picks up. The fault can be cleared by

 

replacing the filter mat (see ordering information for the order number).

How to Replace

Correct the fault in the following steps:

the Filter Mat

 

Step

Action

1

2

3

4

5

6

7

Release the filter subdrawer.

Swivel the filter subdrawer downwards and pull it forwards and out.

Remove the old filter mat.

Insert a new filter mat in the filter subdrawer.

Place the distance grid on the new filter mat.

Insert the filter subdrawer in the guide rails, slide it back and swivel it up so that it locks in place.

Press the Reset button.

Result:± Fault LEDs for ªAlarm,º ªFan 1,º ªFan 2º and ªFan 3º go off.

± Contacts 11 and 12 are closed in the ªAlarmº relay.

4-46

System Manual

C79000-G8576-C199-06

Page 112
Image 112
Siemens S5-135U/155U appendix Replacing Filter Mat Inadequate Air, Flow, Correct the fault in the following steps