Mitsumi electronic PLA-ABA installation manual Electrical work, Explanation of word

Models: PLA-ABA

1 56
Download 56 pages 54.94 Kb
Page 10
Image 10
 Explanation of word

6. Electrical work

Function table

Select unit number 00

Mode

Settings

 

 

Mode no.

Setting no. Initial setting

setting

Power failure automatic recovery

Not available

 

01

1

 

 

Available

*1

2

 

 

 

 

 

Indoor temperature detecting

Indoor unit operating average

 

 

 

1

 

 

Set by indoor unit’s remote controller

 

02

2

 

 

Remote controller’s internal sensor

 

 

 

3

 

LOSSNAY connectivity

Not Supported

 

 

 

1

 

 

Supported (indoor unit is not equipped with outdoor-air intake)

03

2

 

 

Supported (indoor unit is equipped with outdoor-air intake)

 

 

3

 

Power voltage

230 V

 

04

1

 

 

208 V

 

2

 

 

 

 

 

 

Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])

 

 

 

 

 

Mode

Settings

 

 

Mode no.

Setting no. Initial setting

setting

Filter sign

100Hr

 

 

 

1

 

 

2500Hr

 

07

2

 

 

No fi lter sign indicator

 

 

 

3

 

Fan speed

Silent

 

 

 

1

 

 

Standard

 

08

2

 

 

High ceiling

 

 

 

3

 

No. of air outlets

4 directions

 

 

 

1

 

 

3 directions

 

09

2

 

 

2 directions

 

 

 

3

 

Installed options (high-performance fi lter)

Not supported

 

 

10

1

 

 

Supported

 

 

2

 

 

 

 

 

 

Up/down vane setting

Equipped with vanes (vanes angle setup

)

 

 

1

 

 

Equipped with vanes (vanes angle setup

)

 

11

2

 

 

Equipped with vanes (vanes angle setup

)

 

 

3

 

*1 When the power supply returns, the air conditioner will start 3 minutes later.

*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.

6.3.3How to set the fixed up/down air direction (Only for wired remote controller and PUZ-A/PUY-A•NHA application)

Only the particular outlet can be fixed to certain direction with the procedures below. Once fi xed, only the set outlet is fi xed every time air conditioner is turned on. (Other outlets follow UP/DOWN air direction setting of the remote controller.)

Manual background Explanation of word

"Refrigerant address No." and "Unit No." are the numbers given to each air conditioner.

"Outlet No." is the number given to each outlet of air conditioner.

Horizontal airflow

Remote controller setting The airflow direction of

this outlet is controlled by the airflow direction setting of remote contoller.

Downward

Fixed setting

The airflow direction of this outlet is fixed

in particular direction.

Manual background When it is cold because of direct airflow, the airflow direction can be fixed horizontally to avoid direct airflow.

(Refer to the right.)

• "Up/Down air direction" is the direction (angle) to fi x.

Reset

1

2

3

4

5

 

horizontal

 

 

 

 

Outlet No.3

Outlet No.4

MITSUBISHI

ELECTRIC

label

Outlet No.2

Outlet No.1

Note: "0" indicates all outlets.

 

10