TEST RUN

7. Test run

7.1. Before test run

After completing installation and the wiring and piping of the indoor and out- door units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply. Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0 M .

Do not carry out this test on the control wiring (low voltage circuit) termi- nals.

Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M.

TEST RUN

 

 

 

 

COOL, HEAT

 

°F

 

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

SIMPLE

 

 

TEMP.

 

 

ON/OFF

 

 

MENU

ON/OFF

 

FILTER

BACK

MONITOR/SET

DAY

 

CHECK

TEST

PAR-21MAA

CLOCK

OPERATION

CLEAR

 

 

 

 

 

Fig. 7-1

ON/OFF button

Test run display

Indoor temperature liquid pipe temperature display

ON/OFF lamp

Power display

Error code display

Test run remaining time display Set temperature button

Mode selection button

Air direction button

TEST button

Fan Speed button Louver button

7.2. Test run

The following 3 methods are available.

7.2.1. Using wired remote controller (Fig. 7-1)

Turn on the power at least 12 hours before the test run.

Press the [TEST] button twice. “TEST RUN” liquid crystal display

Press the [Mode selection] button and switch to the cooling (or heating) mode.

Make sure that cold (or warm) wind is blown out.

Press the [Fan speed] button. Make sure that the wind speed is switched.

Press the [Air direction button] or [Louver button].

Check operation of the vane or louver.

Check operation of the outdoor unit fan.

Release test run by pressing the [ON/OFF] button. Stop

Register a telephone number.

The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the opera- tion manual for the indoor unit.

7.2.2. Using wireless remote controller (Fig. 7-2)

Turn on the power to the unit at least 12 hours before the test run.

Press the button twice continuously.

(Start this operation from the status of remote controller display turned off.)

TEST RUN and current operation mode are displayed.

 

TESTRUN

 

ON/OFF

TEMP

 

FAN

AUTO STOP

MODE

VANE

AUTO START

,

 

 

CHECK

LOUVER

h

TEST RUN

 

min

SET

RESET CLOCK

Press the MODE

button to activate

mode, then check whether

cool air is blown out from the unit.

Press the MODE

button to activate

mode, then check whether

warm air is blown out from the unit.

Press the FAN button and check whether fan speed changes.

Press the VANE button and check whether the auto vane operates properly. Press the ON/OFF button to stop the test run.

Note:

Point the remote controller towards the indoor unit receiver while following steps to .

It is not possible to run the TEST RUN in FAN, DRY or AUTO mode.

Fig. 7-2

 

 

ERROR CODE

 

 

 

TEMP.

 

 

ON/OFF

 

 

MENU

ON/OFF

 

FILTER

BACK

MONITOR/SET

DAY

 

CHECK

TEST

PAR-21MAA

CLOCK

OPERATION

CLEAR

 

ERROR CODE

CHECK

ON/OFF TEMP

 

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

h

TEST RUN

 

min

SET

RESET CLOCK

7.2.3.Using SW4 in outdoor unit

Refer to the outdoor unit installation manual.

7.3. Self-check

7.3.1.Wired remote controller (Fig. 7-3)

Turn on the power.

Press the [CHECK] button twice.

Set refrigerant address with [TEMP] button if system control is used.

Press the [ON/OFF] button to stop the self-check.

CHECK button

Refrigerant address

TEMP. button

IC: Indoor unit

OC: Outdoor unit

Check code

Unit address

7.3.2.Wireless remote controller (Fig. 7-4)

Turn on the power.

Press the CHECK button twice.

(Start this operation from the status of remote controller display turned off.)

begins to light.

ERROR CODE

Fig. 7-4

Fig. 7-3

“00” begins to blink.

h

While pointing the remote controller toward the unit’s receiver, press the button. The check code will be indicated by the number of times that the buzzer sounds from the receiver section and the number of blinks of the operation lamp.

Press the ON/OFF button to stop the self-check.

13

Page 13
Image 13
Mitsumi electronic PLA-ABA installation manual Test run, Before test run, Self-check

PLA-ABA specifications

Mitsumi Electric, a leading manufacturer in the electronic components sector, has made significant strides in audio equipment with the development of the PLA-ABA, a premium audio amplifier. This device is engineered to deliver exceptional sound quality while integrating advanced technologies that enhance its performance and usability.

One of the standout features of the PLA-ABA is its class-D amplifier architecture. This design ensures high efficiency, allowing the device to operate coolly even under heavy load conditions. The amplifier boasts a power output that can drive a wide range of speaker systems, making it suitable for both casual listeners and audio professionals. With a total harmonic distortion (THD) level that is notably low, users can experience pristine audio reproduction without the unwanted artifacts that often plague lower-quality amplifiers.

In addition to its robust performance characteristics, the PLA-ABA is equipped with advanced digital signal processing (DSP). This technology allows for various audio enhancement features, including equalization settings that can be adjusted to suit different musical genres or personal preferences. The user-friendly interface makes it easy to navigate through these settings, ensuring that users can customize their audio experience effortlessly.

Connectivity is another facet where the PLA-ABA excels. It supports multiple input options, including AUX, optical, and Bluetooth, making it versatile for various setups, whether for home theater systems or portable use. The integration of Bluetooth technology not only enables wireless streaming from smartphones and tablets but also ensures a stable connection with minimal latency, making it perfect for both music streaming and gaming.

Durability is paramount in the design of the PLA-ABA. The chassis is constructed from high-grade materials that not only provide a sleek aesthetic but also protect internal components from electromagnetic interference and physical damage. This attention to ruggedness makes the amplifier suitable for both stationary and mobile applications.

Moreover, Mitsumi has placed a strong emphasis on energy efficiency with the PLA-ABA. The device incorporates features that help reduce power consumption when not in use, contributing to a smaller carbon footprint, while still delivering the high-quality audio performance that users expect.

In summary, the Mitsumi electronic PLA-ABA represents a blend of cutting-edge technology and practical design, making it a formidable choice for audiophiles and casual users alike. Its combination of class-D amplification, advanced DSP, versatile connectivity options, and durable construction positions it as a leading product in its category, setting a benchmark for future audio amplifiers.