clearances

clearances

ILDV20/ILDV30 Fireplace Insert

INSERT Clearances

no combustibles (ie: drapes, doors) may be within, or swing within 36" of the front of the insert.

Top

Combustible

 

 

Facing

Mantel

 

 

 

Facing

Side Wall

Side

 

12”

(305 mm)

9”

INSERT ClearancesFacingFigure 3mantel clearancesHEARTH REQUIREMENTSManual backgroundManual backgroundManual backgroundManual backgroundManual background (228 mm)

10” (254 mm)

Minimum

12” (305 mm) Manual background Minimum

42” (1067 mm)

Minimum

Figure 3

Mantel Clearances

12” (305 mm)

Maximum Depth

3/4” (19 mm) Maximum Depth Combustible Facing

NOTE: Side clearance to com- bustibles is 10" (254 mm) from opening whether it is side wall or mantel legs.

FP1947

mantel clearances

NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed

in this manual.

HEARTH REQUIREMENTS

The insert must be installed on a noncombustible hearth extending a minimum of 12" from the fireplace opening (local codes may require a larger hearth). The hearth must also extend to both

sides of the face (Refer to the table on Page 7).