ILDV20/ILDV30 Fireplace Insert | INSERT installation |
WARNING
Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
CAUTION
A manual
NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada
A listed manual shutoff is factory installed upstream of appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. Figure 13.
IMPORTANT: The main gas valve is for turning on or shutting off the gas to the insert.
Check your building codes for any special requirements for |
|
| |
CAUTION |
| ||
locating equipment shutoff valve to inserts. |
| ||
Apply pipe joint sealant lightly to threads. This will prevent | Use pipe joint sealant that is resistant | ||
| |||
excess sealant from going into pipe. Excess sealant in pipe |
| to liquid petroleum (LP) gas. | |
could result in clogged burner system valves. |
|
| |
We recommend that you install a sediment trap/drip leg in |
|
| |
supply line as shown in Figure 13. Locate sediment trap/drip |
|
|
leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
Approved Flexible Gas Line Supplied with Appliance
Natural Gas
From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
Figure 13
Gas Connection
Tee Joint
Pipe Nipple
Cap
18 | 83D0511 |