INSERT INSTALLATION

INSERT INSTALLATION

ILDV20/ILDV30 Fireplace Insert

check gas type

Use proper gas type for the insert you are installing. If you have conflicting gas type, do not install insert. See dealer where you purchased the insert for proper insert according to your gas type.

Install gas piping to insert location

WARNING

A qualified installer or service person must connect appliance to gas supply. Follow all local codes.

CAUTION

For propane/LP units, never connect insert directly to the propane/ LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply.

installation items needed

Make sure you have the items listed below before installing appliance.

External regulator (supplied by installer)

Piping (check local codes)

Test gauge connection*

Sealant (resistant to propane/LP gas)

Sediment trap (optional but recommended)

Tee joint

Pipe wrench

 

approved flexible gas line with gas connector (if allowed by local codes — not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of wa- ter. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing

rain or sleet.

External

100 gal. (min.

Propane/LP

Regual-

Supply Tank

tor

 

Vent

 

Pointing

 

Down

 

 

FP1930

Figure 12 - External Regulator with Vent Pointing Down (Propane/LP Only)

CAUTION

Use only new black iron or steel pipe. Inter- nally tinned copper or copper tubing can be used per National Fuel Gas Code, Section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (listed on data plate) at the maximum flow rate (BTU/hr). Undue pressure loss will occur if the pipe is too small.

83D0511

17

Page 17
Image 17
Monessen Hearth ILDV20PV, ILDV20NV, ILDV30NV Insert Installation, check gas type, Install gas piping to insert location