Reserved and Special Software Commands.  | 
  | |
CLEAR | Writes 0's and CR's to memory.  | 
  | 
LOAD [F6] | Loads memory. Not same function as Basic F3 key.  | 
  | 
EXIT [F5] | Required to close comm port, close file, and clear error traps.  | 
  | 
comma [,]  | Do not use comma to separate elements of 545 commands (T,L, and ?  | M  | 
xx). Comma is a Basic symbol; use space instead.  | 
  | |
[a,b,c]  | 
  | |
C  | Continuous Step Mode is normally not used with the CY545 unless  | 
  | 
motion can be terminated with an external Abort signal. Refer also  | to the  | 
CY550 which is an advanced version which has a larger  | selection of   | 
software commands.  | 
  | 
Special Aspects of Some Commands.
WThe Wait command causes the 545 to wait at the instruction, therefore incoming stop commands will not be processed. Use a T command in a jump to itself.
L, Z  | These loop instructions assume that the first pass of a routine  | 
  | before reaching the loop command was the 1st loop pass. In  | 
  | general, the loop count must be one less than required. Also  | 
  | see J & T below.  | 
T,H,W,O | These commands are followed by a numeric value in Hexdecimal  | 
  | which is desinated by the H following the value. The decimal and  | 
  | the hex values for 0 to 7 are the same and the H can be omitted.  | 
H  | Homing is a single step operation. The Busy signal is not  | 
  | continuously set during homing but cycles every step. It is best  | 
  | therefore that homing is executed from memory.  | 
J, T  | Any Jump or Test operation, which includes L & Z commands,  | 
  | must not cross the memory page boundry which is ever 256  | 
  | bytes; 256, 512, 768, 1024, etc. Use the Y for global jumps.  | 
Installation and Test Procedure
1.Connect AC power cord.
2.Connect motors, verify that driver current is correct for motors. See Appendix C for current adjustment and Appendix D for motor wiring.
3.Connect CI cable. Limit Loop must be closed for motor to run.
4.Connect the serial cable and 
5.Connect the AC power and 
that: AC neon; power is present. DC lamp; motor power (VMM) is OK. All  | SMC | 
LEDs are off except for BUSY.  | 
  |