EDS-408A/405A Series User’s Manual

Specifications

Power

 

 

Input Voltage

12 to 45 VDC, redundant inputs

 

Input Current (@24V)

Max. 0.26A: (EDS-408A/405A)

 

 

Max. 0.43A: (EDS-408A/405A-MM-SC,

 

 

EDS-408A/405A-SS-SC,

 

 

EDS-408A/405A-MM-ST)

 

Connection

One removable 6-pin terminal block

 

Overload Current Protection

Present

 

Reverse Polarity Protection

Present

 

Mechanical

 

 

Dimensions

53.6 ⋅ 135 ⋅ 105 mm (W ⋅ H ⋅ D)

 

Weight

0.65 kg

 

Installation

DIN-Rail, Wall Mounting (optional kit)

 

Casing

IP30 protection, metal case

 

Environment

 

 

Operating Temperature

0 to 60°C (32 to 140°F)

 

 

-40 to 75°C (-40 to 167°F) for -T models

 

Storage Temperature

-40 to 85°C (-40 to 185°F)

 

Ambient Relative Humidity

5% to 95% (non-condensing)

 

Regulatory Approvals

 

 

Safety

UL60950 (E212360), UL 508, CSA C22.2 No. 60950,

 

EN60950 (pending)

 

EMI

FCC Part 15, CISPR (EN55022) class A

 

EMS

EN61000-4-2 (ESD), Level 3

 

 

EN61000-4-3 (RS), Level 3

 

 

EN61000-4-4 (EFT), Level 3

 

 

EN61000-4-5 (Surge), Level 3

 

 

EN61000-4-6 (CS), Level 3

 

Shock

IEC60068-2-27

 

Freefall

IEC60068-2-32

 

Vibration

IEC60068-2-6

 

WARRANTY

5 years

 