DCA-70SSJU SERIES — GENERATOR OUTPUTS/GAUGE READING
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly re- lated to the voltage being supplied at either the UVWO ter- minals or the 3 twist lock auxilliary receptacles.
Tables 9 and 10 show what amount of current is available at the GFCI receptacles when the UVWO terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the recep- tacles.
Table 9. GFCI Receptacle Load Capability
KVA in Use | Available Load Current |
(UVWO Terminals) | (AMPS) |
3Ø 240/480V | GFCI Duplex NEMA |
| |
82 | 0 |
77.8 | 5 amps per receptacle |
73.7 | 10 amps per receptacle |
69.5 | 15 amps per receptacle |
65.4 | 20 amps per receptacle |
Table 10. GFCI Receptacle Load Capability
KW in Use | Available Load Current |
(AMPS) | |
1Ø 240/120V | GFCI Duplex NEMA |
| |
60 | 0 |
58.8 | 5 amps per receptacle |
57.6 | 10 amps per receptacle |
56.4 | 15 amps per receptacle |
55.2 | 20 amps per receptacle |
How to Read the Output Terminal Gauge.
The gauge and selector switch on the control panel DO NOT effect the generator output. They are provided to help ob- serve how much power is being supplied, produced at the UVWO terminals lugs.
When the Voltage selector switch is in the 3Ø,240/139V position (See Figure 16), place the AC Voltmeter Change- Over Switch (Figure 17) to the
Use this position for 3Ø, 208V/1Ø,120V
Figure 16. Voltage Selector Switch 240/139V Three Phase
Position (for 3Ø, 208V, 120V voltage)
Figure 17. AC Voltmeter | Figure 18 | AC Voltmeter | |||
| Gauge | ||||
| (Volt reading on | ||||
|
|
|
| ||
|
| 20 | 40 | ||
0 |
|
| 60 | ||
| |||||
|
|
|
| ||
| 75 |
A
Figure 19. AC Ammeter | Figure 20. AC Ammeter |
(Amp reading on U lug) |
NOTE | The ammeter and voltmeter |
gauges are only active when the | |
| UVWO terminals are in use. |