Multiquip DCA25USI manual Output Terminal Panel Connections, UVWO Terminal Output Voltages

Models: DCA25USI

1 80
Download 80 pages 9.28 Kb
Page 26
Image 26
OUTPUT TERMINAL PANEL CONNECTIONS

OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the UVWO output terminal lugs. The voltages at the terminals are dependent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3.Turn the voltage regulator knob (Figure 21) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fine tuning of the output voltage is required.

Figure 21. Voltage Regulator Knob

3Ø-240/139 UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 19.

3Ø-208V/1Ø-120V UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 22.

Figure 19. Voltage Selector Switch

3Ø-240/139V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 20.

Figure 20. UVWO Terminal Lugs

3Ø-240/139V Connections

Figure 22. Voltage Selector Switch

3Ø-240/139V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 23.

Figure 23. UVWO Terminal Lugs

3Ø-208/1Ø-120V Connections Connections

UVWO Terminal Output VoltagesNOTICE

To achieve a 3Ø 208V output the voltage selector switch must be in the 3Ø-240/139 position and the voltage regulator must be adjusted to 208V..

page 26 — DCA25Usi 60 hz Generator • operation and parts manual — rev. #3 (07/19/11)

Page 26
Image 26
Multiquip DCA25USI manual Output Terminal Panel Connections, UVWO Terminal Output Voltages