3Ø-480/277V UVWO Terminal Output Voltages

OUTPUT TERMINAL PANEL CONNECTIONS

3Ø-480/277V UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 3Ø 480/277 position as shown in Figure 24.

1Ø-240/120V UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 1Ø 240/120 position as shown in Figure 26.

Figure 24. Voltage Selector Switch

3Ø-480/277V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 25.

Figure 25. UVWO Terminal Lugs

3Ø-440/254V Connections

3.Turn the voltage regulator knob (Figure 21) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fine tuning of the output voltage is required.

Figure 26. Voltage Selector Switch

1Ø-240/120V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 27.

Figure 27. UVWO Terminal Lugs

1Ø-200/100V Connections

3.Turn the voltage regulator knob (Figure 21) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fine tuning of the output voltage is required.

1Ø-240/120V UVWO Terminal Output VoltagesNOTICE

ALWAYS make sure that the connections to the UVWO terminals are secure and tight.The possibility of arcing exists, that could cause a fire.