page 24 — DCa40sskU/kU4i 60 hz generaTor • operaTion anD parTs manUal — rev. #1 (03/11/13)
GeneratOr Outputs

generaTor oUTpUT volTages

A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.

voltage selector switch

The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch

voltage selector switch locking Button

To lock the voltage selector switch, press and hold the
red button located at the bottom of the switch. While
holding the red button down, insert a pad lock into the hole
next to the button to retain it in the inward locked position.
When the lock is removed, the red button is spring loaded
and will return to its normal outward unlocked position.
CaUTion
never change the position of the voltage selector
switch while the engine is running. alWaYs place
circuit breaker in the oFF position before selecting
voltage.
Table 7. voltages available
UvWo output
Terminal lugs
voltage selector switch
3-phase 240/139v position
voltage selector switch
3-phase 480/270v position
line-line 208V 220V 240V 416V 440V 480V
line-neutral 120V 127V 139V 240V 254V 277V
voltage selector switch single-phase 240/120v position
line-neutral/
line-line
120V
Line-Neutral N/A N/A 240V
Line-Line N/A N/A

generator amperage

Table 8 shows the maximum amps the generator can
provide. Do noT exceed the maximum amps as listed..

gFCi receptacle load Capability

The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
Table 8. generator maximum amps
rated voltage maximum amps
1Ø 120 Volt 82 amps (4 wire)
89A x 2 (Zigzag)
1Ø 240 Volt 41 amps (4 wire)
89A (Zigzag)
3Ø 240 Volt 89 amps
3Ø 480 Volt 44 amps
Table 9. 1Ø gFCi receptacle load Capacity
kW in Use
Twist lock (C6369)
available load
Current (amps)
1Ø 240/120V GFCI Duplex
5-20R 120V
21.0 0
19.8 5 amps/receptacle
18.6 10 amps/receptacle
17.4 15 amps/receptacle
16.2 20 amps/receptacle
Table 10. 3Ø generator maximum amps
kva in Use
(UvWo Terminals)
available load
Current (amps)
3Ø 240/480V GFCI Duplex
5-20R 120V
37 0 amps/receptacle
32.8 5 amps/receptacle
28.7 10 amps/receptacle
24.5 15 amps/receptacle
20.4 20 amps/receptacle