Programming the GEM-P816 & GEM-P1632
01 | INTERIOR | BYPASS | FIRE/TBL SYS TBL | CHIME |
INTERIOR BYPASS | FIRE/TBL SYS TBL | CHIME |
(Direct Entry)
Total Number of Zones in Area 1 (Appears for New Panel Only)
Press the Abutton and then directly enter the total number of zones to be
programmed for Area 1. Valid entries are from 01 to 32. Directly enter the total number of zones, including leading zeros. Use number buttons 1through
9. NOTE: Press the 0 button for a zero. The system is based on
groups of 4 zones each (after the first 8 zones), and will automatically round up to the next group of 4. For example, if you enter 18, it will automatically
convert this to 20 zones. Press Jto save. Press NEXT (E) button to
proceed. NOTE: If you are programming a 2 Area system, enter the total number of zones required for Areas 1 & 2. The Direct Address Program Mode can then be used to remove zones from Area 1 and place them in Area 2. See Zone Options. If Programming a Wireless Only system, or using wireless only on Zones
03 | INTERIOR | BYPASS | FIRE/TBL SYS TBL | CHIME |
|
INTERIOR BYPASS | FIRE/TBL SYS TBL | CHIME |
(Press YES or NO)
Panel Zone Doubling?(Appears for New Panel Only)
Press the Abutton. If the total number of zones in Area 1 entered was 16 or greater, press YES (E) to effectively double the capacity of the control
panel's hard wired zones from 8 to 16. The 16 zones will no longer be EOL zones, but will be designated for Normally Closed devices only. The terminal for Zone 1 will now support Zones 1 and 9 with the use of the supplied EZ Zone DoublingTM resistors, E & Z supplied. (Refer to Wiring Diagram and Installation Instructions). If Panel Zone doubling is not desired, press NO (E). NOTE: Answer NO for
04 | INTERIOR | BYPASS | FIRE/TBL SYS TBL | CHIME |
|
INTERIOR BYPASS FIRE/TBL SYS TBL CHIME
(Press YES or NO)
05 | INTERIOR | BYPASS | FIRE/TBL | SYS TBL | CHIME |
| |||||
| INTERIOR | BYPASS | FIRE/TBL | SYS TBL | CHIME |
(Press YES or NO)
Fire Zones in Area 1 (Appears for New Panel Only) Press the A
button and then directly enter the zone number of any zones which are to be used as Fire Zones (both
Jto save, and then repeat for any additional zone(s). Press NEXT (E)
button to proceed.
previous question) which are to be used with
leading zeros. Press Jto save and then repeat for any additional zone(s).
NOTE: Only zones which have been designated as Fire Zones may be pro- grammed as 2 Wire Fire zones. Press NEXT (E) button to proceed.
NOTE: JP3 must be set to
GEMINI |
|
|
|
|
|
|
| |
|
|
|
| ENT INTERIOR | BYPASS | FIRE/TBL | SYS TBL | CHIME |
06 NEXT/YES |
|
|
|
| ||||
A | 1 | 2 | 3 | E |
|
|
|
|
D PRIOR/NO |
|
|
|
| ||||
B | 4 | 5 | 6 | F |
|
|
|
|
AREA |
|
|
|
| ||||
C | 7 | 8 | 9 | 0 G |
|
|
|
|
COMPUTERIZED SECURITY SYSTEM |
|
|
|
| ||||
|
|
|
| INTERIOR | BYPASS | FIRE/TBL | SYS TBL | CHIME |
(Yes or No)
Report all Zones to Central Station?(Appears for New Panel Only)
Press YES (E) button for all zones to report to central station; press NO (F) button for no zones to report (LOCAL SYSTEM).
5