ADJUSTMENTS

28

ADJUSTMENTS

PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.

FIGURE64

VENTURI ADJUSTMENT

Natural gas models have air shutters set at 1/4 (.250") inch open. Propane gas models have air shutters set at 7/16 (.437) inch open. Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be established.

FIGURE66

FIGURE65

WARNING: This is a fast act- ing thermocouple. It is an in- tegral safety component. Replace only with a fast act- ing thermocouple supplied by Wolf Steel Ltd.

AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED GAS INSTALLER!

RESTRICTING VERTICAL VENTS

Vertical installations may display a very active flame.If this appearance is not desirable,the vent exit must be restricted

using the optional restrictor vent kit, RP40-KT. This will reduce

the velocity of the exhaust gases,slowing down the flame pattern and creating a more traditional gentle appearance. Specific instructions are included with the kit.