Napoleon Fireplaces BGD42N Using Flexible Vent Components, Horizontal Air Terminal Installation

Models: BGD42N BGD42P

1 28
Download 28 pages 35.93 Kb
Page 14
Image 14
USING FLEXIBLE VENT COMPONENTS

14

USING FLEXIBLE VENT COMPONENTS

Use only approved aluminum flexible liner kits marked:

"Wolf Steel Approved Venting" as identified by the stamp only on the 7” outer liner.

HORIZONTAL AIR TERMINAL INSTALLATION

AVENT SHIELD MUST BE USED IF THE WALL TERMINAL IS INSTALLED ON COMBUSTIBLE, EXTERIOR SURFACES.

1.Cut or frame a hole in an exterior wall with a minimum round or square opening of 10½ inches. Secure the firestop spacer over the opening to the interior wall.

2.Stretch the 5" diameter aluminum flexible liner to the required length taking into account the additional length needed for the finished wall surface. Slip the liner a mini- mum of 2" over the inner sleeve of the air terminal and secure with 3 #8 screws. Apply a heavy bead of the high temperature sealant.

3.Using the 8" diameter flexible aluminum liner, slide over the outer combustion air sleeve of the air terminal and secure with 3 #8 screws. Seal as before.

FIGURE 18

The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return flange.

FIGURE 19

4.Insert the liners through the firestop maintaining the required clearance to combustibles. Holding the air termi- nal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).

For safe and proper operation of the fireplace, follow the venting instructions exactly.

All inner exhaust and outer intake vent pipe joints may be sealed using either Red RTV high temp silicone seal- ant or Black high temp Mill Pac with the exception of the fireplace exhaust flue collar which must be sealed us- ing Mill Pac (not supplied).

5.Apply a heavy bead of the high temperature sealant, Mill Pac, to the inside of the 5" liner approximately 1" from the end. Slip the liner a minimum of 2" over the fireplace vent collar and secure with 3 #8 screws.

6.Using the 8" diameter flexible aluminium liner, apply sealant, slide a minimum of 2" over the fireplace combus- tion air collar and secure with 3 #8 screws.

7.If more liner needs to be used to reach the fireplace, couple them together as illustrated. The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use noncombustible strapping to maintain the minimum 1" clearance to combustibles.

8.The heat shield must

be installed only when ter-

FIGURE 20

minating horizontally with

 

no vertical rise. Remove

 

the two screws nearest

 

the vent collars on the top

 

of the fireplace. Align the

 

vent shield (supplied) and

 

secure.

 

VERTICAL AIR TERMINAL INSTALLATION

1.Fasten the roof support to the roof using the screws provided.

The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the

authority having

ROOF SUPPORT

jurisdiction or the optional

r o o f

support.

2.Stretch the inner aluminum flex liner to the required length. Slip the liner a minimum of 2” over the inner sleeve of the air terminal connector

INNER and secure with 3 #8 screws. Seal SLEEVEusing a heavy bead of the high

temperature sealant.

AIR

3. Repeat using the outer aluminum flex

CONNECTOR

liner.

TERMINAL

 

4.Thread the air terminal connector / liner assembly down through the roof.

HIGH

 

The air terminal must be located

SEALANT

 

TEMPERATURE

 

INNER FLEX

 

vertically and plumb. Attach the air

LINER

 

terminal connector to the roof support,

OUTER FLEX

LINER

 

ensuring that the top of the air terminal

DO NOT CLAMP

is 16” above the highest point that it

THE FLEXIBLE

penetrates the roof.

ALUMINUM LINER

W415-0533 / E / 02.09.06

Page 14
Image 14
Napoleon Fireplaces BGD42N, BGD42P manual Using Flexible Vent Components, Horizontal Air Terminal Installation