New Buck Corporation 94NC Minimum Clearance Masonry Insert, Section, Masonry Insert Installation

Models: 94NC

1 29
Download 29 pages 51.28 Kb
Page 7
Image 7
MASONRY INSERT INSTALLATION

SECTION II

MASONRY INSERT INSTALLATION

The Model 94NC may be installed using an all masonry

fireplace built in accordance with

Uniform Building Code and National

Fire Protection Association (NFPA). The first step in

this type of installation is to determine

acceptability of

fireplace and chimney for use with

a woodstove.

Both

construction

and condition

of fireplace

are important

consid-

erations when

installing a woodstove. The chimney should extend at

least 3' above

roof and

at least 2' above any point of

roof within 10'.

 

 

 

CAUTION

REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE BEFORE YOU INSTALL YOUR STOVE. “DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.”

MINIMUM CLEARANCE MASONRY INSERT

MODEL 94NC

A. Side Wall Combustible

12"

B. Front Floor Protector

16"

C. Side Floor Protector

8"

D. Side Wood Trim

10"

E. Top Wood Trim

18"

F. Mantel or Brackets

24"

E

F

 

D

C

B

 

A

1.The hearth must be of masonry construction and must extend a minimum of 16" in front of firebox opening and a minimum of 8" to either side of firebox opening.

Minimum floor protection under unit must have an R-value of 0.30.

2. If there is not minimum hearth protection from front of firebox opening and front of masonry hearth, a floor protector must be used in front of hearth to protect combustible materials. The floor protector must be 3/8" minimum thickness non-combustible material or equivalent.(See Page 12,13).