INSTALLATION

EXTERIOR VENT LOCATIONS and RESTRICTIONS

INSIDE CORNER DETAIL

TERMINATION BOX, LOCATION CHART

G

V

A

D

E

 

V

L

V

 

B

H

 

 

C

FIXED

 

E

B

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

FIXED

 

 

 

 

 

 

V

 

CLOSED

B

 

 

 

 

 

 

 

 

A

 

CLOSED

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

F

V

 

 

O

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

B

B

V

 

 

J

A

I

 

 

 

 

 

 

 

V

 

A

 

 

OPENABLE

 

 

 

 

 

 

K

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V = VENT TERMINAL

A = AIR SUPPLY INLET

 

= AREA WHERE TERMINAL IS NOT PERMITTED

 

 

 

A.Clearance above grade, veranda, porch, deck, or balcony (*12 inches (30cm) minimum)

B.Clearance to window or door that may be opened (*12 inches (30cm) minimum.)

C.Clearance to permanently closed window (minimum 12 inches (30 cm)) recommended to prevent condensation on window.

D.Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (60cm) from the center-line of the terminal (18 inches (46cm) minimum.)

E.Clearance to unvented soffit (12 inches (30cm) minimum.)

F.Clearance to outside corner - 6 inches (15 cm)

G.Clearance to inside corner - 12 inches (30 cm)

H.*Not to be installed above a meter regulator assembly within 3 feet (90 cm) horizontally from the centerline of the regulator.

I.Clearance to service regulator vent outlet (*6 feet (1.8 m) minimum.)

J.Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance (*12 inches (30 cm) minimum.)

K.Clearance to a mechanical air supply inlet (*6 feet (1.8 m) minimum.)

L.Clearance above paved sidewalk or a paved driveway located on public property (*7 feet (2.1m) minimum).

M.Clearance under veranda, porch, deck, or balcony, (*12 inches (30 cm) minimum).

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

As specified in “M” above, only permitted if verandas, porches, decks, or balconies are fully open a minimum of two sides beneath the floor.

*As specified in CGA B1:19 Installation Codes (1991). NOTE: Local codes or regulations may require different clearances.