Preparing Floor Opening(s)
1.Mark fl oor opening(s) as shown in Figure 6. Provide minimum clearances at rear and right side walls of closet or alcove for installation of furnace and wiring.
2.Cut floor opening on outside edge of marked line so that opening is slightly larger than area marked.
3.Additional provisions may be necessary for optional air conditioning or heat pump if refrigerant lines are installed elsewhere than at the front of the furnace.
4.The refrigerant and entrance supply opening dimensions may be adjusted ± 1/2”.
Installing Duct Connector
NOTE: The duct connector is designed for use on ducts down to 12” wide. On typical ducts, the fi nger tab duct connector may be installed using Method B. On narrow ducts, there may be insuffi cient clearance to bend the tabs on two sides of the fi nger tab duct connector. In such
|
| If "X" | Use Duct Connector | |||
| floor cavity is: | Model Part Number | ||||
English | Metric | Finger | Screw | |||
(mm) | Tab | Down | ||||
|
|
| ||||
7/8" |
| 22 | 901987 | 904008 | ||
| 2" |
| 51 | 901988 | 904009 | |
4 | 1/4" |
| 108 | 901989 | 904010 | |
6 | 1/4" |
| 159 | 901990 | 904011 | |
8 | 1/4" |
| 210 | 901991 | 904012 | |
10 1/4" |
| 260 | 901992 | 904013 | ||
12 1/4" |
| 311 | 901993 | 904014 |
Table 4. Floor Cavity Sizes
cases, use Method C or D. For screw down duct connector use method E. For Platinum models always use method A.
Method A - Platinum Series
NOTE: Flex duct used must have a minimum temperature rating of 200° F and meet all other applicable codes and standards.
1.Place duct connector through opening in fl oor. See Figure 9.
2.Connect 14” supply duct.
| REAR WALL OF ENCLOSURE | |||
|
| Center Line |
| |
|
|
|
| |
(60 mm) |
|
|
|
|
|
|
|
| Furnace |
|
|
| Outline | |
|
|
|
| |
|
| (368 mm) |
|
|
17" |
|
|
| |
(432 mm) |
|
|
| |
|
| (368 mm) |
| |
|
|
| ||
|
|
| ||
|
|
| (422 mm) | |
(603 mm) |
|
|
|
|
| Optional Supply Wire |
|
| |
| Entrance |
|
| |
| A/C Or HP |
| 3" (76 mm) | |
(Not required |
|
| ||
Optional |
|
| ||
(95 mm) |
|
| ||
for Platinum) |
|
| ||
| Refrigerant |
|
| |
|
| Line |
|
|
3/4" | 5" |
| ||
(19 mm) |
| |||
(108 mm) | (127 mm) | (86 mm) |
| |
|
| |||
Furnace Outer |
| 10" |
| |
Door | (254 mm) | 20" | (159 mm) | |
|
|
|
| |
|
| (508 mm) |
|
Figure 6. Downflow Floor Cutout Locations (nominal dimensions)
11